← Back to summary See all parameters LE SOUICH · Liencourt
SIAEP DE LA FONTAINE
Water safety Water safety Parameter Unfiltered tap water Allowed range Filtered Free Chlorinemg CL2/l 0.15 ● (Near the limit) 0.2 – 1 0.003 ▲ Total Chlorinemg CL2/l 0.2 No limit 0.04
General General Parameter Unfiltered tap water Allowed range Filtered TemperatureC 15.8 No limit 15.8 Hardnessmg CaCO3/l 334.9 80 – 459 334.9 Hardness fF 33.5 No limit 33.5 pH 7.4 6.5 – 9.5 7.4 TurbidityNTU 0.1 ≤ 4 0.01 ColorColor Units 5 ≤ 15 5 ConductivityμS / cm 650 ≤ 2,500 650 TDSmg/l 416estimated 0 – 1,199 416 Alkalinitymg CaCO3/l 292 No limit 292 Bicarbonatemg HCO3/l 356 No limit 356
Pathogens Pathogens Parameter Unfiltered tap water Allowed range Filtered eColiUFC/100ml 0 ≤ 0 0 BacteriasNMP/100ml 0 ≤ 0 0 EnterococcusUFC/100ml 0 ≤ 0 0
Chemical parameters Chemical parameters Parameter Unfiltered tap water Allowed range Filtered Cyanide totalμg CN/l 10 ≤ 50 0.5 Fluoridemg F/l 0.1 ≤ 1.5 0.03 Mercuryμg Hg/l 0.01 ≤ 1 0.001 Nitritesmg NO2/l 0.01 ≤ 0.5 0.004 Nitratesmg NO3/l 32 ≤ 50 9.6
Minerals Minerals Parameter Unfiltered tap water Allowed range Filtered Magnesiummg/l 3.1 No limit 3.1 Calciummg/l 127 No limit 127 Potassiummg/l 1 No limit 1 Chloridemg/l 22.5 ≤ 250 22.5
Metals Metals Parameter Unfiltered tap water Allowed range Filtered Aluminiumμg/l 10 ≤ 200 10 Antimonyμg/l 1 ≤ 5 1 Arsenicμg/l 2 ≤ 10 1 Bariumμg/l 30 ≤ 1,000 30 Cadmiumμg/l 1 ≤ 5 1 Chromiumμg/l 5 ≤ 50 5 Copperμg/l 21 ≤ 2,000 1.05 Ironμg/l 10 ≤ 200 10 Manganeseμg/l 10 ≤ 50 10 Leadμg/l 2 ≤ 10 0.1 Nickelμg/l 5 ≤ 20 5 Seleniumμg/l 2 ≤ 10 2 Sodiummg/l 8.8 ≤ 200 8.8
Chlorine by-products Chlorine by-products Parameter Unfiltered tap water Allowed range Filtered Trichloroethyleneμg/l 0.1 No limit 0.005 Total Trihalomethanesμg/l 5.84 ≤ 100 0.29
Haloacetic acids Haloacetic acids Parameter Unfiltered tap water Allowed range Filtered Total haloacetic acidsμg/l 0.8 ≤ 60 0.04
Pesticides Pesticides Parameter Unfiltered tap water Allowed range Filtered Total pesticidesug/L 0.31 ≤ 0.5 0.31
Herbicides Herbicides Parameter Unfiltered tap water Allowed range Filtered D 2 4ug/L 0.02 ≤ 70 0.02 Atrazineug/L 0.005 ≤ 3 0.005
Perfluorinated chemicals Perfluorinated chemicals Parameter Unfiltered tap water Allowed range Filtered PFOAug/L 0.001 No limit 0.001 PFOSug/L 0.001 No limit 0.001 PFNAug/L 0.001 No limit 0.001 Total PFASug/L 0.003 ≤ 0.1 0 PFAS 4ng/l Not reported No limit — PFAS 21ng/l Not reported No limit —
Other Other Parameter Unfiltered tap water Allowed range Filtered Ammoniamg/l 0.01 No limit 0.003 Perchlorateug/L 0.42Sampled Jan 2026 No limit 0.42 Sulfatemg/l 14.6 No limit 14.6 Uraniumug/L 10 No limit 10
Data from the French health inspection of drinking water (Ministry of Health, regional health agencies), per distribution unit. Quality ranges are based on WHO guidelines, EU Directive 2020/2184 and the French public health code.
Your Water Quality
Independent information about tap water quality in France.
Brought to you by