Skip to content
Filter your tap water with TAPP Water
TappwaterYour Water Quality
← Back to summary

See all parameters

CITRON · Camopi

MAIRIE DE CAMOPI

Water safety

Water safety
ParameterUnfiltered tap waterAllowed rangeFiltered
Free Chlorinemg CL2/lNot reported0.2 – 1—

General

General
ParameterUnfiltered tap waterAllowed rangeFiltered
TemperatureC26Sampled Mar 2026No limit26
Hardnessmg CaCO3/l41 (Near the limit)80 – 45941
Hardness fF4.1No limit4.1
pH6.1 (Near the limit)6.5 – 9.56.1
TurbidityNTU4.6 (Near the limit)≤ 40.46
ColorColor Units20 (Outside the range)≤ 1520
ConductivityμS / cm137≤ 2,500137
TDSmg/l87.7estimated0 – 1,19987.7
Alkalinitymg CaCO3/l60No limit60

Pathogens

Pathogens
ParameterUnfiltered tap waterAllowed rangeFiltered
ClostridiumUFC/100ml80≤ 08
eColiUFC/100ml64≤ 06.4
BacteriasNMP/100ml80≤ 08
EnterococcusUFC/100ml12≤ 01.2

Chemical parameters

Chemical parameters
ParameterUnfiltered tap waterAllowed rangeFiltered
Mercuryμg Hg/lNot reported≤ 1—
Nitritesmg NO2/l0.05≤ 0.50.02
Nitratesmg NO3/l1≤ 500.3

Minerals

Minerals
ParameterUnfiltered tap waterAllowed rangeFiltered
Chloridemg/l3.54≤ 2503.54

Metals

Metals
ParameterUnfiltered tap waterAllowed rangeFiltered
Arsenicμg/lNot reported≤ 10—
Ironμg/l5,343 (Outside the range)≤ 2005,343
Manganeseμg/l280 (Outside the range)≤ 50280
Leadμg/lNot reported≤ 10—

Perfluorinated chemicals

Perfluorinated chemicals
ParameterUnfiltered tap waterAllowed rangeFiltered
Total PFASug/LNot reported≤ 0.1—
PFAS 4ng/lNot reportedNo limit—
PFAS 21ng/lNot reportedNo limit—

Other

Other
ParameterUnfiltered tap waterAllowed rangeFiltered
Ammoniamg/l0.05No limit0.015
Sulfatemg/l1No limit1

Data from the French health inspection of drinking water (Ministry of Health, regional health agencies), per distribution unit. Quality ranges are based on WHO guidelines, EU Directive 2020/2184 and the French public health code.