LA GARE-MARLANGES (LA CHAPELLE GENESTE) · Berbezit
DIRECTION EAU ET ASSAINISSEMENT (CAPEV)
Water safety
Water safety
Parameter
Unfiltered tap water
Allowed range
Filtered
Free Chlorinemg CL2/l
0.15 ● (Near the limit)
0.2 – 1
0.003 ▲
Total Chlorinemg CL2/l
0.17
No limit
0.034
General
General
Parameter
Unfiltered tap water
Allowed range
Filtered
TemperatureC
19.4
No limit
19.4
Hardnessmg CaCO3/l
9 ● (Near the limit)
80 – 459
9 ●
Hardness fF
0.9
No limit
0.9
pH
5.8 ▲ (Outside the range)
6.5 – 9.5
5.8 ▲
TurbidityNTU
0.3
≤ 4
0.03
ColorColor Units
5
≤ 15
5
ConductivityμS / cm
42
≤ 2,500
42
TDSmg/l
26.9estimated
0 – 1,199
26.9
Alkalinitymg CaCO3/l
12
No limit
12
Pathogens
Pathogens
Parameter
Unfiltered tap water
Allowed range
Filtered
eColiUFC/100ml
0
≤ 0
0
BacteriasNMP/100ml
0
≤ 0
0
EnterococcusUFC/100ml
0
≤ 0
0
Chemical parameters
Chemical parameters
Parameter
Unfiltered tap water
Allowed range
Filtered
Mercuryμg Hg/l
Not reported
≤ 1
—
Nitritesmg NO2/l
0.01
≤ 0.5
0.004
Nitratesmg NO3/l
1.9
≤ 50
0.57
Minerals
Minerals
Parameter
Unfiltered tap water
Allowed range
Filtered
Chloridemg/l
3.6
≤ 250
3.6
Metals
Metals
Parameter
Unfiltered tap water
Allowed range
Filtered
Arsenicμg/l
0.87Sampled Feb 2025
≤ 10
0.44
Leadμg/l
Not reported
≤ 10
—
Perfluorinated chemicals
Perfluorinated chemicals
Parameter
Unfiltered tap water
Allowed range
Filtered
PFOAug/L
0.002Sampled Mar 2026
No limit
0.002
PFOSug/L
0.002Sampled Mar 2026
No limit
0.002
PFNAug/L
0.002Sampled Mar 2026
No limit
0.002
Total PFASug/L
0.005Sampled Mar 2026
≤ 0.1
0.001
PFAS 4ng/l
Not reported
No limit
—
PFAS 21ng/l
Not reported
No limit
—
Other
Other
Parameter
Unfiltered tap water
Allowed range
Filtered
Ammoniamg/l
0.01
No limit
0.003
Sulfatemg/l
2.5
No limit
2.5
Data from the French health inspection of drinking water (Ministry of Health, regional health agencies), per distribution unit. Quality ranges are based on WHO guidelines, EU Directive 2020/2184 and the French public health code.