← Back to summary See all parameters SIAEP DE CHATILLON-LES-SONS · Assis-sur-Serre
SIAEP DE SONS ET CHATILLON
Water safety Water safety Parameter Unfiltered tap water Allowed range Filtered Free Chlorinemg CL2/l 0.19 ● (Near the limit) Sampled Jan 2026 0.2 – 1 0.004 ▲ Total Chlorinemg CL2/l 0.23Sampled Jan 2026 No limit 0.046
General General Parameter Unfiltered tap water Allowed range Filtered TemperatureC 7Sampled Jan 2026 No limit 7 Hardnessmg CaCO3/l 360Sampled Sept 2025 80 – 459 360 Hardness fF 36Sampled Sept 2025 No limit 36 pH 7.4Sampled Jan 2026 6.5 – 9.5 7.4 TurbidityNTU 0.3Sampled Jan 2026 ≤ 4 0.03 ColorColor Units 5Sampled Jan 2026 ≤ 15 5 ConductivityμS / cm 695 ≤ 2,500 695 TDSmg/l 444.8estimated 0 – 1,199 444.8 Alkalinitymg CaCO3/l 272Sampled Jan 2026 No limit 272 Bicarbonatemg HCO3/l 332Sampled Jan 2026 No limit 332
Pathogens Pathogens Parameter Unfiltered tap water Allowed range Filtered eColiUFC/100ml 0Sampled Jan 2026 ≤ 0 0 BacteriasNMP/100ml 0Sampled Jan 2026 ≤ 0 0 EnterococcusUFC/100ml 0Sampled Jan 2026 ≤ 0 0
Chemical parameters Chemical parameters Parameter Unfiltered tap water Allowed range Filtered Cyanide totalμg CN/l 10Sampled Jan 2026 ≤ 50 0.5 Fluoridemg F/l 0.13Sampled Jan 2026 ≤ 1.5 0.039 Mercuryμg Hg/l 0.015Sampled Jan 2026 ≤ 1 0.002 Nitritesmg NO2/l 0.01Sampled Jan 2026 ≤ 0.5 0.004 Nitratesmg NO3/l 51 ● (Near the limit) ≤ 50 15.3
Minerals Minerals Parameter Unfiltered tap water Allowed range Filtered Magnesiummg/l 7.9Sampled Jan 2026 No limit 7.9 Calciummg/l 123Sampled Jan 2026 No limit 123 Potassiummg/l 1.1Sampled Jan 2026 No limit 1.1 Chloridemg/l 26Sampled Jan 2026 ≤ 250 26
Metals Metals Parameter Unfiltered tap water Allowed range Filtered Aluminiumμg/l 10Sampled Jan 2026 ≤ 200 10 Antimonyμg/l 0.5Sampled Jan 2026 ≤ 5 0.5 Arsenicμg/l 0.5Sampled Jan 2026 ≤ 10 0.25 Bariumμg/l 24.8Sampled Jan 2026 ≤ 1,000 24.8 Cadmiumμg/l 0.5Sampled Jan 2026 ≤ 5 0.5 Chromiumμg/l 0.9Sampled Jan 2026 ≤ 50 0.9 Copperμg/l 5Sampled Jan 2026 ≤ 2,000 0.25 Ironμg/l 5Sampled Jan 2026 ≤ 200 5 Manganeseμg/l 0.5Sampled Jan 2026 ≤ 50 0.5 Leadμg/l 0.5Sampled Jan 2026 ≤ 10 0.025 Nickelμg/l 1.2Sampled Jan 2026 ≤ 20 1.2 Seleniumμg/l 1.8Sampled Jan 2026 ≤ 10 1.8 Sodiummg/l 8.5Sampled Jan 2026 ≤ 200 8.5
Chlorine by-products Chlorine by-products Parameter Unfiltered tap water Allowed range Filtered Trichloroethyleneμg/l 1Sampled Jan 2026 No limit 0.05 Total Trihalomethanesμg/l 10.1Sampled Jan 2026 ≤ 100 0.51
Haloacetic acids Haloacetic acids Parameter Unfiltered tap water Allowed range Filtered Total haloacetic acidsμg/l 1.2Sampled Jan 2026 ≤ 60 0.06
Pesticides Pesticides Parameter Unfiltered tap water Allowed range Filtered Total pesticidesug/L 3.04 ▲ (Outside the range) Sampled Jan 2026 ≤ 0.5 3.04 ▲
Herbicides Herbicides Parameter Unfiltered tap water Allowed range Filtered D 2 4ug/L 0.02Sampled Jan 2026 ≤ 70 0.02 Atrazineug/L 0.006Sampled Jan 2026 ≤ 3 0.006
Perfluorinated chemicals Perfluorinated chemicals Parameter Unfiltered tap water Allowed range Filtered PFOAug/L 0.001Sampled Jan 2026 No limit 0.001 PFOSug/L 0.001Sampled Jan 2026 No limit 0.001 PFNAug/L 0.001Sampled Jan 2026 No limit 0.001 Total PFASug/L 0.029Sampled Jan 2026 ≤ 0.1 0.003 PFAS 4ng/l Not reported No limit — PFAS 21ng/l Not reported No limit —
Other Other Parameter Unfiltered tap water Allowed range Filtered Ammoniamg/l 0.05Sampled Jan 2026 No limit 0.015 Perchlorateug/L 3.4Sampled Jan 2026 No limit 3.4 Sulfatemg/l 17.4Sampled Jan 2026 No limit 17.4 Uraniumug/L 10Sampled Jan 2026 No limit 10
Data from the French health inspection of drinking water (Ministry of Health, regional health agencies), per distribution unit. Quality ranges are based on WHO guidelines, EU Directive 2020/2184 and the French public health code.
Your Water Quality
Independent information about tap water quality in France.
Brought to you by
tappwater.co
Data from the French health inspection of drinking water (Ministry of Health, regional health agencies), per distribution unit. Quality ranges are based on WHO guidelines, EU Directive 2020/2184 and the French public health code.