ROCHEFORT SUR LA COTE · Aillianville

MAIRIE DE ROCHEFORT SUR LA COTE

Water safety

Water safety
ParameterUnfiltered tap waterAllowed rangeFiltered
Free Chlorinemg CL2/l1.75 (Outside the range)0.2 – 10.035
Total Chlorinemg CL2/l1.8No limit0.36

General

General
ParameterUnfiltered tap waterAllowed rangeFiltered
TemperatureC20.1No limit20.1
Hardnessmg CaCO3/l35880 – 459358
Hardness fF35.8No limit35.8
pH7.66.5 – 9.57.6
TurbidityNTU0.4≤ 40.04
ColorColor Units5Sampled Feb 2026≤ 155
ConductivityμS / cm640≤ 2,500640
TDSmg/l409.6estimated0 – 1,199409.6
Alkalinitymg CaCO3/l317No limit317

Pathogens

Pathogens
ParameterUnfiltered tap waterAllowed rangeFiltered
ClostridiumUFC/100ml0≤ 00
eColiUFC/100ml0≤ 00
BacteriasNMP/100ml0≤ 00
EnterococcusUFC/100ml0≤ 00

Chemical parameters

Chemical parameters
ParameterUnfiltered tap waterAllowed rangeFiltered
Mercuryμg Hg/lNot reported≤ 1—
Nitritesmg NO2/l0.01≤ 0.50.004
Nitratesmg NO3/l1.7≤ 500.51

Minerals

Minerals
ParameterUnfiltered tap waterAllowed rangeFiltered
Magnesiummg/l34No limit34
Calciummg/l86No limit86
Chloridemg/l8.1≤ 2508.1

Metals

Metals
ParameterUnfiltered tap waterAllowed rangeFiltered
Arsenicμg/lNot reported≤ 10—
Leadμg/lNot reported≤ 10—

Chlorine by-products

Chlorine by-products
ParameterUnfiltered tap waterAllowed rangeFiltered
Total Trihalomethanesμg/l10.6≤ 1000.53

Perfluorinated chemicals

Perfluorinated chemicals
ParameterUnfiltered tap waterAllowed rangeFiltered
PFOAug/L0.002Sampled Sept 2025No limit0.002
PFOSug/L0.002Sampled Sept 2025No limit0.002
PFNAug/L0.002Sampled Sept 2025No limit0.002
Total PFASug/L0.005Sampled Sept 2025≤ 0.10.001
PFAS 4ng/lNot reportedNo limit—
PFAS 21ng/lNot reportedNo limit—

Other

Other
ParameterUnfiltered tap waterAllowed rangeFiltered
Ammoniamg/l0.05No limit0.015
Sulfatemg/l43No limit43

Data from the French health inspection of drinking water (Ministry of Health, regional health agencies), per distribution unit. Quality ranges are based on WHO guidelines, EU Directive 2020/2184 and the French public health code.